NIHGC LTD
NIHGC LTD

Installation Testers   


The Fluke 1652/PKIT Electricians Kit provides a complete solution to installation test requirements, including those for Part P. Containing an installation tester, a 2-pole tester, a socket tester and Part P certificates, the kit offers a substantial saving over purchase of the products individually. The kit comprises of the Fluke 1652 Multifunction Installation Tester, which tests to the requirements of BS7671 IEE 16th Edition wiring regulations and offers automatic RCD testing and a remote probe; a Fluke T120 2-pole Tester, a Fluke SM200 Socket Tester and a Fluke TD07 Part P certificate pad.

Model Name Description Price List
Fluke 1652C Multifunction Installation Tester

  • 6 AA Cell batteries
  • C1600 Hard carrying case
  • Zero Adapter
  • Mains test cord
  • TL165X/STD Standard Test Lead Set
  • Padded carrying strap
  • Quick reference guide
  • TP165X Remote control probe and lead¹
  • Users manual on CD-ROM
On Request
Fluke T130 Voltage/Continuity Tester With LCD, Switchable Load On Request
Fluke SM200 Socket Master Tester On Request
TD07 Part P Certificate Pad On Request

Extra functionality, faster testing, and as rugged as ever

The 1652C Installation Tester builds upon the rugged reputation of the earlier 1650 Series, only it’s re-designed to meet your need for more productive test tools.

This installation tester offers the following new capabilities:

  • Fast high current loop test
  • Variable RCD current mode for customized settings
  • PASS/FAIL indication for RCD tests
  • Select voltage measurement between L-N, L-PE and N-PE
  • Zero adapter for easy test lead compensation, available as new accessory and also included with standard scope of supply
  • Extended documentation mode (UK only)

Safer, easier installation testing.

The 1652C Installation Tester verify the safety of electrical installations in domestic, commercial and industrial applications. It can ensure that fixed wiring is safe and correctly installed to meet the requirements of IEC 60364, HD 384 and all relevant local standards.

Faster

  • Two measurements at once and a dual display. PEFC/PSC and loop impedance are measured and displayed in parallel, saves you more than 50% of test time compared to other loop testers.
  • Additional new high current loop mode. Faster measurements compared to loop tests with non-trip mode for RCD’s.
  • Unique zero adapter for fast, always reliable and accurate test lead and mains cord compensation.
  • Fast voltage measurement between L-N, L-PE and N-PE using the mains cord. No need to change measurement connections.

Safer

  • Earth Volt Touchpad detects raised earth voltages >50 V, indicating potential dangerous situations.
  • Supplied with the SureGrip™ test leads and clips which gives the user a comfortable, reliable grip.

Easy

  • Rotary dial knob indicates clear which function is selected, all functionalities on one spot and no complex multi level menus.
  • Large display with backlight, clear symbols and exceptionally wide viewing angle for easy and safe readings.
  • PASS/FAIL indication for RCD test results.
  • Variable RCD current mode for customized settings.
  • Extended documentation mode (UK only)

AC Voltage Measurement
Range:  500 V
Resolution:  0.1 V
Accuracy (50 – 60 Hz)  ± (0.8% + 3 digits)
Input Impedance  3.3 MΩ
Overload Protection  660 Vrms
Continuity Testing
Range (autoranging):  20 Ω, 200 Ω, 2000 Ω
Resolution:  0.01 Ω, 0.1 Ω, 1 Ω
Test Current:  > 200 mA
Open Circuit Voltage:  > 4 V
Accuracy:  ± (1.5%+3 digits)
Insulation Resistance Measurement
Test Voltage:  250 – 500 – 1000 V
Test Voltage:  250 V
Test Current:  1 mA @ 250 kΩ
Range/Resolution:  20 MΩ/0.01 MΩ
Range/Resolution:  200 MΩ/0.1 MΩ
Accuracy:  ± (1.5% + 3 digits)
Test Voltage:  500 V
Test Current:  1 mA @ 500 kΩ
Range/Resolution:  20 MΩ/0.01 MΩ
Range/Resolution:  200 MΩ/0.1 MΩ
Accuracy:  ± (1.5% + 3 digits)
Range/Resolution:  500 MΩ/1 MΩ
Accuracy:  10%
Test Voltage:  1000 V
Test Current:  1 mA @ 1 MΩ
Range/Resolution:  20 MΩ/0.01 MΩ
Range/Resolution:  200 MΩ/0.1 MΩ
Accuracy:  ± (1.5% + 3 digits)
Range/Resolution:  500 MΩ/1 MΩ
Accuracy:  10%
Auto Discharge:  Discharge time constant, 0.5 second for
C = 1 µF or less
Live Circuit Detection:  Inhibits test if terminal voltage > 30 V prior to initiation of test
Maximum Capacitive Load:  Operable with the 5 µF load
Loop Impedance Measurement (High Current Mode and Non-Trip Mode)
Range:  100 – 500 VAC (50/60 Hz)
Input connection:  Soft Key selection
Loop impedance:  Phase to earth
Line impedance:  Phase to neutral
Limit on consecutive tests:  Automatic thermal shutdown after 50 consecutive tests at 10 second intervals (typical)
Max. Test Current. High Current and Non-Trip Modes:
Maximum Test Current @ 400 V  20 A sinusoidal for 10 ms
Maximum Test Current @ 230 V  12 A sinusoidal for 10 ms
Range/Resolution:  20 Ω/0.01 Ω
Range/Resolution:  200 Ω/0.1 Ω
Range/Resolution:  2000 Ω/1 Ω
Accuracy (no Trip mode):  ± (3% + 6 digits)
Accuracy (Hi Current mode):  ± (2% + 4 digits)
PFC, PSC Test
Computation:  PFC or PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance
Range:  0 – 25 kA
Resolution (Ik < 1000 A):  1 A
Resolution (Ik >= 1000 A):  0.1 kA
Accuracy:  Determined by accuracy of loop resistance and mains voltage measurements.
RCD Testing ¹
G  General, no delay
S  Time delay
A  Responds to pulsed signal
AC  Responds to AC
Tripping Time Test (ΔT)
Trip Time Accuracy  ±(1% Reading + 1 digit)
Multiplier:  x ½
Current Settings:  10, 30, 100, 300, 500, 1000 mA
Current Accuracy:  +0% – 10%
RCD Type ¹:  G
Measurement Range:  310 ms (Europe), 2000 ms (UK)
RCD Type ¹:  S
Measurement Range:  510 ms (Europe), 2000 ms (UK)
Multiplier  x 1
Current Settings:  10, 30, 100, 300, 500, 1000 mA
Current Accuracy:  +10% – 0%
RCD Type ¹:  G
Measurement Range:  310 ms
RCD Type ¹:  S
Measurement Range:  510 ms
Multiplier:  x 5
Current Settings:  10, 30 mA
Current Accuracy:  ±10%
RCD Type ¹:  G
Measurement Range:  50 ms
RCD Type ¹:  S
Measurement Range:  160 ms
Tripping Current (ramp)
Current Range:  50% – 110% of RCD’s rated current
Step Size:  10% of IΔN
Dwell time (Type G): ¹  300 ms / step
Dwell time (Type S): ¹  500 ms / step
Trip Current Measurement Accuracy:  ±5%
Phase Sequence Indication
Icon:  Icon Phase Sequence indicator is active
Display of Phase Sequence:
 Displays ‘1-2-3’ in digital display field for correct sequence.
 Displays ‘3-2-1’ for incorrect phase.
 Dashes in place of a number indicate a valid determination could not be made.

A solid, basic installation tester.

The Fluke 1662 gives you Fluke reliability, simple operation and all the testing power you need for day-in, day-out installation testing.

The Fluke 1662 puts more power in your hands by quickly and efficiently testing to all local regulations.

Measurement functions

  • Measurement function
  • Voltage & frequency
  • Wiring polarity checker, detects broken N wires
  • Insulation resistance
  • Continuity & resistance
  • Measure motor windings with continuity test
  • Loop & line resistance
  • Prospective earth fault current (PEFC/IK)
  • Prospective short-circuit current (PSC/IK)
  • RCD switching time
  • RCD tripping level (ramp test)
  • Measures trip time & current for RCD type A & AC in one test
  • RCD variable current
  • Automatic RCD test sequence
  • Phase sequence indicator

Other features

  • On/Off switchable auto-start for RCD & Looptest
  • Self-test
  • Illuminated display
  • Time and date (when used with optional FlukeView software)

Included accessories

  • Heavy duty, single input line cord
  • Hard case
  • Remote control probe
  • Zero adapter

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Accuracy of tTest voltage (at rated test current) +10%, -0%
Test voltage 100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω / 0.001 Ω / High current mΩ mode
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type A4, AC¹, G², S³
Notes ¹Responds to AC
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
Step size 10% of IΔN²
Dwell time Type G 300 ms/step
Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
Phase Sequence Indication
Icon icon phase sequence indicator  Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 Kg
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

Protect appliances, share results wirelessly, perform seven tests with one touch

The Fluke 1664 FC Installation Tester is the only tester with “Insulation PreTest.” If the tester detects that an appliance is connected to the system under test, it stops the insulation test, helping eliminate accidental damage. The 1664 FC also gives you Fluke Connect®, so you can send test results to your smartphone and collaborate with others. Auto Test makes performs seven tests with one press of the button, reducing the number of manual connections and decreasing the possibility of making errors.

Insulation pretest

Protect the installation. Avoid costly mistakes.

The Fluke 1664 FC Installation Tester is the only Installation with “Insulation PreTest,” which warns you about potentially serious and costly mistakes. If the tester detects that an appliance is connected to the system under test, it will stop the insulation test and provide a visual warning. This helps eliminate accidental damage to peripheral equipment and keeps your customers happy.

Fluke Connect and FlukeCloud™ Storage

Share from anywhere.

Stay on the same page even when you and your team are in different places. Fluke Connect allows your 1664 FC Installation Tester to send test results to your smartphone so you can connect and collaborate with others. It’s the fastest way to let your team see what you see, helping you get approvals without leaving the field.

Retrieve stored results from anywhere

FlukeCloud™ storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. Plus you can import the data into Fluke DMS to process and generate certificates. Plus you get world-class data protection. Safe. Secure. Fast. More accurate. All from the power of Fluke Connect.

Auto Test reduces test time up to 40%

Auto Test performs 5 required installation tests in one sequence, ensuring compliance with local installation regulations. It reduces the number of manual connections, decreases the possibility of making errors and reduces test time up to 40% from previous Fluke models.

The 1664 FC puts more power in your hands by quickly and efficiently testing to all local regulations, protecting appliances that may be inadvertently connected to the system under test, and making it easy to share test results over your smartphone.

  • Autotest to test line/loop impedance, RCD trip current / trip time, insulation tests with a single connection and the press of a single button.
  • Additional high current loop mode. Faster measurements compared to loop tests with non-trip mode for RCDs.
  • Z-max memory for loop tests – easy evaluation of the highest loop test value.
  • Unique zero adapter for fast, always reliable and accurate test lead and mains cord compensation.
  • Fast voltage measurement between L-N, L-PE and N-PE using the mains cord. No need to change measurement connections.
  • Measure RCD trip current & trip time in parallel (RCD type AC and A).
  • Two measurements at once and a dual display. PEFC or PSC and loop impedance are measured and displayed in parallel, saving you time.
  • Ring testing – select the required input sockets with soft keys – no need to exchange test leads.
  • Automatic test start for Loop & RCD tests – as soon as mains voltage is stable it starts testing.
  • Earth Volt Touchpad detects raised earth voltages >50 V, indicating potential dangerous situations.
  • Supplied with the safety designed SureGrip™ test leads and clips which gives the user a comfortable, reliable grip and consistent results.
  • Rotary dial knob indicates clearly which function is selected, all in one spot with no complex multi-level menus.
  • Large display with backlight, clear symbols and with exceptionally wide viewing angle for easy and safe readings.
  • PASS/FAIL indication for RCD test results.
  • Variable RCD current mode for customized settings.
  • Loop & line resistance with mΩ resolution.
  • Test smooth dc sensitive RCDs (Type B).
  • Extended memory with 3 layers.
  • Use continuity test currents to measure motor windings.
  • Withstands a drop of 1 meter.
  • Compact, lightweight (less than 1.3 kg) and padded neck-strap to free your hands for all day testing.

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Test voltages 50-100-250-500-1000 V
Accuracy of tTest voltage (at rated test current) +10%, -0%
Test voltage 50 V
100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ /50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω / 0.001 Ω / High current mΩ mode
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type AC¹
G²,S³
Model 1664 A, AC, B5, S
Notes ¹Responds to AC
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
Step size 10% of IΔN²
Dwell time Type G 300 ms/step
Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
Earth Resistance Test (RE)
Range 200 Ω / 2000 Ω
Resolution 0.1 Ω / 1Ω
Frequency 128 Hz
Output Voltage 25 V
Phase Sequence Indication
Icon icon phase sequence indicator  Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 Kg
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition